Protective Relay Settings: bus diff protection

bd fig9 f1 to bd fig9 f5

Protective relay settings, coordination parameters, and motor/bus protection data per IEEE C37, IEEE 242, IEC 60255, and IEEE 3004 series. Covers: IEEE C37.112 inverse time-overcurrent curve constants (A, B, p, tr) and IEC 60255-151 constants (k, alpha); CT accuracy classes C100/C200/C400/C800 per IEEE C57.13; relay pickup guidance by ANSI device number; CTI per IEEE 242; motor nameplate voltages, surge withstand levels, vibration limits, and relay alarm/trip thresholds per IEEE 3004.8-2016; ANSI device function numbers for motor and bus protection (Tables B.1/B.2/B.3); online partial discharge assessment thresholds; and dual-tie bus differential CT scheme fault response results per IEEE 3004.11-2019.

Electrical Engineeringparameter type: bus diff protection5 rowsPage 3 of 3
parameter typerecord idbreaker m1breaker m2breaker t1breaker t2bus1 statusbus2 statusfault clearedfault numberfigure numberstandardsubstation configtie bus status
bus diff protectionbd fig9 f1OpenUnaffectedOpenOpenClearedUnaffectedYes19IEEE Std 3004.11-20194 tie CTs external and internal to tie busN/A
bus diff protectionbd fig9 f2OpenUnaffectedOpenOpenDeenergizedUnaffectedYes29IEEE Std 3004.11-20194 tie CTs external and internal to tie busCleared
bus diff protectionbd fig9 f3UnaffectedUnaffectedOpenOpenUnaffectedUnaffectedYes39IEEE Std 3004.11-20194 tie CTs external and internal to tie busCleared
bus diff protectionbd fig9 f4UnaffectedOpenOpenOpenUnaffectedDeenergizedYes49IEEE Std 3004.11-20194 tie CTs external and internal to tie busCleared
bus diff protectionbd fig9 f5UnaffectedOpenOpenOpenUnaffectedClearedYes59IEEE Std 3004.11-20194 tie CTs external and internal to tie busN/A