Protective Relay Settings: ct_saturation

Protective relay settings and coordination parameters per IEEE C37 and IEEE 242. Covers IEEE C37.112-2018 inverse time-overcurrent curve constants (A, B, p, tr) for moderately/very/extremely inverse curves and SEL vendor extensions; IEC 60255-151 curve constants (k, alpha); CT accuracy classes C100/C200/C400/C800 per IEEE C57.13-2016 with burden limits; relay pickup guidance by ANSI device number (50, 51, 50N, 51N, 27, 59, 81U, 81O); coordination time intervals (CTI) per IEEE 242-2001; and CT saturation voltage thresholds.

Electrical Engineeringparameter_type: ct_saturation3 rows
parameter typerecord idcurve designationcurve namecurve standardnotes
ct_saturationsat_voltage_C100C100_satSaturation Knee Voltage C100IEEE C57.13Saturation knee-point voltage >= 100V; CT must withstand 20x rated secondary current without >10% error at rated burden
ct_saturationsat_voltage_C200C200_satSaturation Knee Voltage C200IEEE C57.13Saturation knee-point voltage >= 200V; typical for 15kV class distribution feeders; use ANSI or 90-degree method
ct_saturationsat_voltage_C400C400_satSaturation Knee Voltage C400IEEE C57.13Saturation knee-point voltage >= 400V; required for high-impedance bus differential protection; check CT excitation curve

This is a sample. Search the full protective relay settings dataset and 300+ more by creating a free account and accessing the database.