Protective Relay Settings: relay_pickup

Protective relay settings and coordination parameters per IEEE C37 and IEEE 242. Covers IEEE C37.112-2018 inverse time-overcurrent curve constants (A, B, p, tr) for moderately/very/extremely inverse curves and SEL vendor extensions; IEC 60255-151 curve constants (k, alpha); CT accuracy classes C100/C200/C400/C800 per IEEE C57.13-2016 with burden limits; relay pickup guidance by ANSI device number (50, 51, 50N, 51N, 27, 59, 81U, 81O); coordination time intervals (CTI) per IEEE 242-2001; and CT saturation voltage thresholds.

Electrical Engineeringparameter_type: relay_pickup3 rows
parameter typerecord idcurve designationcurve namecurve standardnotestime dial range maxtime dial range min
relay_pickupdev27_uv27Device 27 UndervoltageANSI IEEEANSI 27 = undervoltage; typical pickup 0.85 pu for motor protection (NEMA MG-1); 0.80 pu for generator loss-of-field; time delay 0.5-3.0s0.90.8
relay_pickupdev50N_ground50NDevice 50N Ground Instantaneous OCANSI IEEEANSI 50N = ground instantaneous OC; set 10-30% of CT secondary rating for sensitive ground detection0.30.1
relay_pickupdev50_phase50Device 50 Phase Instantaneous OCANSI IEEEANSI device 50 = instantaneous overcurrent; set above symmetrical fault current; must NOT pick up on maximum load; pickup = 125-200% max through-fault current21.25