Protective Relay Settings: bus diff protection

bd fig7 f1 to bd fig8 f5

Protective relay settings, coordination parameters, and motor/bus protection data per IEEE C37, IEEE 242, IEC 60255, and IEEE 3004 series. Covers: IEEE C37.112 inverse time-overcurrent curve constants (A, B, p, tr) and IEC 60255-151 constants (k, alpha); CT accuracy classes C100/C200/C400/C800 per IEEE C57.13; relay pickup guidance by ANSI device number; CTI per IEEE 242; motor nameplate voltages, surge withstand levels, vibration limits, and relay alarm/trip thresholds per IEEE 3004.8-2016; ANSI device function numbers for motor and bus protection (Tables B.1/B.2/B.3); online partial discharge assessment thresholds; and dual-tie bus differential CT scheme fault response results per IEEE 3004.11-2019.

Electrical Engineeringparameter type: bus diff protection10 rowsPage 2 of 3
parameter typerecord idbreaker m1breaker m2breaker t1breaker t2bus1 statusbus2 statusfault clearedfault numberfigure numberstandardsubstation configtie bus status
bus diff protectionbd fig7 f1OpenUnaffectedOpenUnaffectedClearedUnaffectedYes17IEEE Std 3004.11-20192 CTs around 1 tie, zone control far tieN/A
bus diff protectionbd fig7 f2OpenOpenOpenOpenClearedDeenergizedYes27IEEE Std 3004.11-20192 CTs around 1 tie, zone control far tieN/A
bus diff protectionbd fig7 f3OpenOpenOpenOpenDeenergizedDeenergizedYes37IEEE Std 3004.11-20192 CTs around 1 tie, zone control far tieCleared
bus diff protectionbd fig7 f4UnaffectedOpenUnaffectedOpenUnaffectedDeenergizedYes47IEEE Std 3004.11-20192 CTs around 1 tie, zone control far tieCleared
bus diff protectionbd fig7 f5UnaffectedOpenUnaffectedOpenUnaffectedClearedYes57IEEE Std 3004.11-20192 CTs around 1 tie, zone control far tieN/A
bus diff protectionbd fig8 f1OpenUnaffectedOpenUnaffectedClearedUnaffectedYes18IEEE Std 3004.11-20192 CTs outside both ties, with 3rd zone logic or summationN/A
bus diff protectionbd fig8 f2UnaffectedUnaffectedOpenOpenNot clearedDeenergizedYes28IEEE Std 3004.11-20192 CTs outside both ties, with 3rd zone logic or summationN/A
bus diff protectionbd fig8 f3UnaffectedUnaffectedOpenOpenUnaffectedUnaffectedYes38IEEE Std 3004.11-20192 CTs outside both ties, with 3rd zone logic or summationCleared
bus diff protectionbd fig8 f4UnaffectedUnaffectedOpenOpenDeenergizedNot clearedYes48IEEE Std 3004.11-20192 CTs outside both ties, with 3rd zone logic or summationN/A
bus diff protectionbd fig8 f5UnaffectedOpenUnaffectedOpenUnaffectedClearedYes58IEEE Std 3004.11-20192 CTs outside both ties, with 3rd zone logic or summationN/A