Protective Relay Settings: coordination

Protective relay settings and coordination parameters per IEEE C37 and IEEE 242. Covers IEEE C37.112-2018 inverse time-overcurrent curve constants (A, B, p, tr) for moderately/very/extremely inverse curves and SEL vendor extensions; IEC 60255-151 curve constants (k, alpha); CT accuracy classes C100/C200/C400/C800 per IEEE C57.13-2016 with burden limits; relay pickup guidance by ANSI device number (50, 51, 50N, 51N, 27, 59, 81U, 81O); coordination time intervals (CTI) per IEEE 242-2001; and CT saturation voltage thresholds.

Electrical Engineeringparameter_type: coordination3 rows
parameter typerecord idcurve designationcurve namecurve standardnotestime dial range maxtime dial range min
coordinationcti_em_relayCTI_EMCTI Electromechanical RelayIEEE 242Minimum CTI 0.30-0.40s between electromechanical OC relay pairs; accounts for relay overshoot and CB interrupting time; overshoot ~0.1s0.40.3
coordinationcti_fuse_relayCTI_FUSECTI Fuse to RelayIEEE 242Minimum CTI 0.10-0.20s between upstream relay and downstream current-limiting fuse; fuse characteristic overlap must be checked0.20.1
coordinationcti_relay_cbCTI_CBCTI Relay to Circuit BreakerIEEE 242CB interrupt time: 3-8 cycles (0.05-0.133s); total CTI = CB time + relay overtravel + safety margin = 0.25-0.40s0.40.25

This is a sample. Search the full protective relay settings dataset and 300+ more by creating a free account and accessing the database.

Get started for FREE