Protective Relay Settings: motor_vibration_limit

Protective relay settings, coordination parameters, and motor/bus protection data per IEEE C37, IEEE 242, IEC 60255, and IEEE 3004 series. Covers: IEEE C37.112 inverse time-overcurrent curve constants (A, B, p, tr) and IEC 60255-151 constants (k, alpha); CT accuracy classes C100/C200/C400/C800 per IEEE C57.13; relay pickup guidance by ANSI device number; CTI per IEEE 242; motor nameplate voltages, surge withstand levels, vibration limits, and relay alarm/trip thresholds per IEEE 3004.8-2016; ANSI device function numbers for motor and bus protection (Tables B.1/B.2/B.3); online partial discharge assessment thresholds; and dual-tie bus differential CT scheme fault response results per IEEE 3004.11-2019.

Electrical Engineeringparameter_type: motor_vibration_limit3 rows
parameter typerecord idacceleration g pk (g peak)displacement mils pk (mils peak-to-peak)mounting typenema frame rangepole countstandardvelocity in s pk (in/s peak)vibration grade
motor_vibration_limitvib_A_resilient_large0.612.4resilient> 440anyIEEE Std 3004.8-20160.15A
motor_vibration_limitvib_A_resilient_med0.612.4resilient210 to 440anyIEEE Std 3004.8-20160.15A
motor_vibration_limitvib_A_resilient_small0.612.4resilient140 to 210anyIEEE Std 3004.8-20160.15A

This is a sample. Search the full protective relay settings dataset and 350+ more by creating a free account and accessing the database.

Get started for FREE

Related data