Protective Relay Settings: motor_surge_withstand

Protective relay settings, coordination parameters, and motor/bus protection data per IEEE C37, IEEE 242, IEC 60255, and IEEE 3004 series. Covers: IEEE C37.112 inverse time-overcurrent curve constants (A, B, p, tr) and IEC 60255-151 constants (k, alpha); CT accuracy classes C100/C200/C400/C800 per IEEE C57.13; relay pickup guidance by ANSI device number; CTI per IEEE 242; motor nameplate voltages, surge withstand levels, vibration limits, and relay alarm/trip thresholds per IEEE 3004.8-2016; ANSI device function numbers for motor and bus protection (Tables B.1/B.2/B.3); online partial discharge assessment thresholds; and dual-tie bus differential CT scheme fault response results per IEEE 3004.11-2019.

Electrical Engineeringparameter_type: motor_surge_withstand3 rows
parameter typerecord iddescriptionrated voltage Vstandardsurge withstand iec kVsurge withstand nema kV
motor_surge_withstandsw_13800Surge withstand voltage for 13800 V rated motors13800 VIEEE Std 3004.8-201660 kV51 kV
motor_surge_withstandsw_2400Surge withstand voltage for 2400 V rated motors2400 VIEEE Std 3004.8-201615 kV9 kV
motor_surge_withstandsw_4160Surge withstand voltage for 4160 V rated motors4160 VIEEE Std 3004.8-201622 kV15 kV

This is a sample. Search the full protective relay settings dataset and 350+ more by creating a free account and accessing the database.

Get started for FREE

Related data