Protective Relay Settings: ct_class

Protective relay settings and coordination parameters per IEEE C37 and IEEE 242. Covers IEEE C37.112-2018 inverse time-overcurrent curve constants (A, B, p, tr) for moderately/very/extremely inverse curves and SEL vendor extensions; IEC 60255-151 curve constants (k, alpha); CT accuracy classes C100/C200/C400/C800 per IEEE C57.13-2016 with burden limits; relay pickup guidance by ANSI device number (50, 51, 50N, 51N, 27, 59, 81U, 81O); coordination time intervals (CTI) per IEEE 242-2001; and CT saturation voltage thresholds.

Electrical Engineeringparameter_type: ct_class3 rows
parameter typerecord idcurve designationcurve namecurve standardnotestime dial range maxtime dial range min
ct_classC100C100Class C100IEEE C57.13Standard relaying burden: 1.0 ohm; terminal voltage: 100V at 20x rated secondary (100A); <10% ratio error; suitable for short relay lead lengths80.5
ct_classC200C200Class C200IEEE C57.13Standard relaying burden: 2.0 ohm; terminal voltage: 200V at 20x rated secondary; <10% ratio error; most common for distribution protection80.5
ct_classC400C400Class C400IEEE C57.13Standard relaying burden: 4.0 ohm; terminal voltage: 400V at 20x rated secondary; <10% ratio error; required for high-impedance differential protection80.5