Protective Relay Settings: ct_burden

Protective relay settings and coordination parameters per IEEE C37 and IEEE 242. Covers IEEE C37.112-2018 inverse time-overcurrent curve constants (A, B, p, tr) for moderately/very/extremely inverse curves and SEL vendor extensions; IEC 60255-151 curve constants (k, alpha); CT accuracy classes C100/C200/C400/C800 per IEEE C57.13-2016 with burden limits; relay pickup guidance by ANSI device number (50, 51, 50N, 51N, 27, 59, 81U, 81O); coordination time intervals (CTI) per IEEE 242-2001; and CT saturation voltage thresholds.

Electrical Engineeringparameter_type: ct_burden3 rows
parameter typerecord idcurve designationcurve namecurve standardnotes
ct_burdenburden_1p0B-1.0Burden B-1 StandardIEEE C57.13Impedance: 1.0 ohm at 60 Hz; PF=0.5; VA=500 at 5A secondary; standard metering burden
ct_burdenburden_2p0B-2.0Burden B-2 StandardIEEE C57.13Impedance: 2.0 ohm at 60 Hz; PF=0.5; VA=1000 at 5A secondary; used for moderate relay burden
ct_burdenburden_4p0B-4.0Burden B-4 StandardIEEE C57.13Impedance: 4.0 ohm at 60 Hz; PF=0.5; VA=2000 at 5A secondary; heavy relay burden