Protective Relay Settings: motor_nameplate_voltage
Protective relay settings, coordination parameters, and motor/bus protection data per IEEE C37, IEEE 242, IEC 60255, and IEEE 3004 series. Covers: IEEE C37.112 inverse time-overcurrent curve constants (A, B, p, tr) and IEC 60255-151 constants (k, alpha); CT accuracy classes C100/C200/C400/C800 per IEEE C57.13; relay pickup guidance by ANSI device number; CTI per IEEE 242; motor nameplate voltages, surge withstand levels, vibration limits, and relay alarm/trip thresholds per IEEE 3004.8-2016; ANSI device function numbers for motor and bus protection (Tables B.1/B.2/B.3); online partial discharge assessment thresholds; and dual-tie bus differential CT scheme fault response results per IEEE 3004.11-2019.
| parameter type | record id | description | nameplate voltage V | nominal voltage V | standard | system type |
|---|---|---|---|---|---|---|
| motor_nameplate_voltage | lv_1ph_120 | LV single-phase 120 V system | 115 V | 120 V | IEEE Std 3004.8-2016 | single-phase |
| motor_nameplate_voltage | lv_1ph_240 | LV single-phase 240 V system | 230 V | 240 V | IEEE Std 3004.8-2016 | single-phase |
| motor_nameplate_voltage | lv_3ph_208 | LV three-phase 208 V system | 200 V | 208 V | IEEE Std 3004.8-2016 | three-phase |