Protective Relay Settings: motor vibration limit

vib B rigid med 246p to vib B rigid med 8p

Protective relay settings, coordination parameters, and motor/bus protection data per IEEE C37, IEEE 242, IEC 60255, and IEEE 3004 series. Covers: IEEE C37.112 inverse time-overcurrent curve constants (A, B, p, tr) and IEC 60255-151 constants (k, alpha); CT accuracy classes C100/C200/C400/C800 per IEEE C57.13; relay pickup guidance by ANSI device number; CTI per IEEE 242; motor nameplate voltages, surge withstand levels, vibration limits, and relay alarm/trip thresholds per IEEE 3004.8-2016; ANSI device function numbers for motor and bus protection (Tables B.1/B.2/B.3); online partial discharge assessment thresholds; and dual-tie bus differential CT scheme fault response results per IEEE 3004.11-2019.

Electrical Engineeringparameter type: motor vibration limit2 rowsPage 2 of 2
parameter typerecord idacceleration g pk (g peak)displacement mils pk (mils peak-to-peak)mounting typenema frame rangepole countstandardvelocity in s pk (in/s peak)vibration grade
motor vibration limitvib B rigid med 246p0.331.3rigid210 to 4402/4/6-poleIEEE Std 3004.8-20160.08B
motor vibration limitvib B rigid med 8p0.241.0rigid210 to 4408+-poleIEEE Std 3004.8-20160.06B