Protective Relay Settings: motor protection setting

ps dev49 alarm to ps dev51N lrg

Protective relay settings, coordination parameters, and motor/bus protection data per IEEE C37, IEEE 242, IEC 60255, and IEEE 3004 series. Covers: IEEE C37.112 inverse time-overcurrent curve constants (A, B, p, tr) and IEC 60255-151 constants (k, alpha); CT accuracy classes C100/C200/C400/C800 per IEEE C57.13; relay pickup guidance by ANSI device number; CTI per IEEE 242; motor nameplate voltages, surge withstand levels, vibration limits, and relay alarm/trip thresholds per IEEE 3004.8-2016; ANSI device function numbers for motor and bus protection (Tables B.1/B.2/B.3); online partial discharge assessment thresholds; and dual-tie bus differential CT scheme fault response results per IEEE 3004.11-2019.

Electrical Engineeringparameter type: motor protection setting6 rowsPage 2 of 2
parameter typerecord iddescriptiondevice numberiec 61850 logical nodenema designationstandardtrip threshold
motor protection settingps dev49 trip sf10Thermal overload (49) trip — service factor 1.049PTTROLIEEE Std 3004.8-2016115% FLA (service factor 1.0)
motor protection settingps dev49 trip sf115Thermal overload (49) trip — service factor 1.1549PTTROLIEEE Std 3004.8-2016125% FLA (service factor 1.15)
motor protection settingps dev50G hrgGround fault (50G) zero-sequence CT — high-resistance grounded system50GIEEE Std 3004.8-2016Set just above system charging current (high resistance grounded)
motor protection settingps dev50G lrgGround fault (50G) zero-sequence CT — low-resistance grounded system50GIEEE Std 3004.8-20165% to 10% of ground fault current (low resistance grounded)
motor protection settingps dev50 tripShort-circuit (50) instantaneous overcurrent trip50PIOCIEEE Std 3004.8-20161.6 to 2 times locked rotor current (set above motor inrush)
motor protection settingps dev51N lrgGround fault (51N) residual — low-resistance grounded system51NPTOCIEEE Std 3004.8-20165% to 10% of ground fault current (low resistance grounded)