Explore the Engineering Database more efficiently by signing up for free. Sign up free

Xfmr-1979-Liq-10M — Transformer

Equipment Type
Transformer
Class Code
Xfmr-1979-Liq-10M
Description
Transformer Liquid Filled >10000 kVA (1979 survey)
Failure Rate per Year (failures/year)
0.0153
Mdt Hours (h)
192
Mttr Hours (h)
1,178.5
Standard
IEEE Std 3006.8-2018
Survey
IEEE 1979 Transformer Survey

Source: IEEE Std 3006.8-2018