E38-112 — Transformer
- Equipment Type
- Transformer
- Class Code
- E38-112
- Description
- Transformer, dry, Air cooled,
- Failure Rate per Year (failures/year)
- 0.001764
- Failures (count)
- 3
- Mdt Hours (h)
- 36.5
- Mtbf Hours (h)
- 4,964,760
- Mttm Hours (h)
- 5.41
- Mttr Hours (h)
- 2
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 1,700.3