Explore the Engineering Database more efficiently by signing up for free. Sign up free
E38-223 — Transformer
- Equipment Type
- Transformer
- Class Code
- E38-223
- Description
- Transformer, liquid, Non-Forced
- Failure Rate per Year (failures/year)
- 0.016812
- Failures (count)
- 11
- Mdt Hours (h)
- 0.65
- Mtbf Hours (h)
- 521,068
- Mttm Hours (h)
- 0.58
- Mttr Hours (h)
- 6.09
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 654.3