Equipment Failure Rates: Transformer

E38-111 to E38-221

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment type: Transformer8 rowsPage 1 of 2
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
TransformerE38-111Transformer, dry, air cooled, ≤0.0026252262.333,337,1482.362.13IEEE Std 3006.8-2018 Table 2USACE PREP86,095.4
TransformerE38-112Transformer, dry, air cooled,0.001764336.54,964,7605.412IEEE Std 3006.8-2018 Table 2USACE PREP1,700.3
TransformerE38-121Transformer, dry, isolation,0.002795192.523,134,1560.9321.26IEEE Std 3006.8-2018 Table 2USACE PREP6,797.8
TransformerE38-211Transformer, liquid, forced air,0.00889522.08985,4180.988.69IEEE Std 3006.8-2018 Table 2USACE PREP5,849.5
TransformerE38-212Transformer, liquid, forced air,0.0382922323.6228,76622.96251IEEE Std 3006.8-2018 Table 2USACE PREP600.6
TransformerE38-213Transformer, liquid, forced air,0.0705193424.34124,22221.69965.33IEEE Std 3006.8-2018 Table 2USACE PREP482.1
TransformerE38-214Transformer, liquid, forced air,1.289753245.36,7922.4311.95IEEE Std 3006.8-2018 Table 2USACE PREP18.6
TransformerE38-221Transformer, liquid, non-forced0.001055632.028,302,26222.33IEEE Std 3006.8-2018 Table 2USACE PREP59,708