E38-212 — Transformer
- Equipment Type
- Transformer
- Class Code
- E38-212
- Description
- Transformer, liquid, Forced air,
- Failure Rate per Year (failures/year)
- 0.038292
- Failures (count)
- 23
- Mdt Hours (h)
- 23.6
- Mtbf Hours (h)
- 228,766
- Mttm Hours (h)
- 22.96
- Mttr Hours (h)
- 251
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 600.6