Explore the Engineering Database more efficiently by signing up for free. Sign up free

E38-212 — Transformer

Equipment Type
Transformer
Class Code
E38-212
Description
Transformer, liquid, Forced air,
Failure Rate per Year (failures/year)
0.038292
Failures (count)
23
Mdt Hours (h)
23.6
Mtbf Hours (h)
228,766
Mttm Hours (h)
22.96
Mttr Hours (h)
251
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
600.6

Source: IEEE Std 3006.8-2018 Table 2

Transformer — class code E38-212 · failure rate per year 0.0382924 failures/year · unit years 600.6 unit-years · mdt hours 23.6 h · failures 23 count | Equipment Failure Rates | Engineering Database