E38-211 — Transformer
- Equipment Type
- Transformer
- Class Code
- E38-211
- Description
- Transformer, liquid, Forced air,
- Failure Rate per Year (failures/year)
- 0.00889
- Failures (count)
- 52
- Mdt Hours (h)
- 2.08
- Mtbf Hours (h)
- 985,418
- Mttm Hours (h)
- 0.98
- Mttr Hours (h)
- 8.69
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 5,849.5
Source: IEEE Std 3006.8-2018 Table 2