Explore the Engineering Database more efficiently by signing up for free. Sign up free
E38-213 — Transformer
- Equipment Type
- Transformer
- Class Code
- E38-213
- Description
- Transformer, liquid, Forced air,
- Failure Rate per Year (failures/year)
- 0.070519
- Failures (count)
- 34
- Mdt Hours (h)
- 24.34
- Mtbf Hours (h)
- 124,222
- Mttm Hours (h)
- 21.69
- Mttr Hours (h)
- 965.33
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 482.1
Source: IEEE Std 3006.8-2018 Table 2