E38-221 — Transformer
- Equipment Type
- Transformer
- Class Code
- E38-221
- Description
- Transformer, liquid, Non-Forced
- Failure Rate per Year (failures/year)
- 0.001055
- Failures (count)
- 63
- Mdt Hours (h)
- 2.02
- Mtbf Hours (h)
- 8,302,262
- Mttm Hours (h)
- 2
- Mttr Hours (h)
- 2.33
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 59,708
Source: IEEE Std 3006.8-2018 Table 2