Clearance Creepage: basic

basic pd3 ovc2 50 to basic pd3 ovc2 600

Minimum electrical clearance and creepage distances per IEC 60664-1:2020 (insulation coordination for low-voltage equipment up to 1000V AC / 1500V DC) and IPC-2221B (PCB conductor spacing). Indexed by insulation type (functional, basic, supplementary, reinforced, double, ipc_pcb), pollution degree (1–3), overvoltage category (I–IV), and working voltage (V). Clearance is shortest air-path distance; creepage is shortest surface-path distance. Critical for PCB layout, enclosure design, and product safety compliance (CE, UL, CSA).

Electrical Engineeringinsulation type: basic2 rowsPage 3 of 3
insulation typerecord idaltitude correction factorapplication noteclearance mm (mm)creepage mm (mm)material groupovervoltage categorypollution degreestandardworking voltage V (V)
basicbasic pd3 ovc2 501Basic insulation; PD3 (industrial with condensation risk); OVC II; material group I0.81.5III3IEC60664-150
basicbasic pd3 ovc2 6001Basic insulation; PD3; OVC II; 600V36.3III3IEC60664-1600