ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: warewashing7 rowsPage 3 of 3
factor typeitem idapplianceheat gain latent W (W)heat gain sensible convective W (W)heat gain sensible radiant W (W)heat gain total W (W)sub typesupply water flow rate Ls (L/s)usage factor (dimensionless)water temperature C (C)
warewashingwarewash 021Upright door type3,8101,02604,836high temperature under a 0.9 × 0.9 m hood at 142 L/s182
warewashingwarewash 022Upright door type2,31546902,784high temperature under a 1.5 × 1.2 m hood at 236 L/s182
warewashingwarewash 0231120 mm conveyor5,86129306,154high temperature under a 0.9 m hood at 472 L/s0.11188
warewashingwarewash 024Ducted 1680 mm conveyor dishwasher4,9531,8463,10710.11820
warewashingwarewash 025Ducted flight type conveyor dishwasher6,5352,6083,92710.06880
warewashingwarewash 026Ducted flight type conveyor dishwasher with heat recovery4,6601,0553,60510.06880
warewashingwarewash 027Ducted flight type conveyor dishwasher with blow dryer10,8144,6016,21310.06880