Cooling Load Factors: warewashing

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor_type: warewashing3 rows
factor typeitem idapplianceheat gain latent W (W)heat gain sensible convective W (W)heat gain sensible radiant W (W)heat gain total W (W)sub typesupply water flow rate Ls (L/s)water temperature C (C)
warewashingwarewash_001Pre-rinse spray valve2,4622,4035910.04490
warewashingwarewash_002Pre-rinse spray valve3,5173,4298810.08490
warewashingwarewash_003Pre-rinse spray valve4,3674,04432210.25490