Cooling Load Factors: luminaire_heat_fractions

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor_type: luminaire_heat_fractions3 rows
factor typeitem idluminaire categoryradiative fraction max (dimensionless)radiative fraction min (dimensionless)space fraction max (dimensionless)space fraction min (dimensionless)
luminaire_heat_fractionsluminaire_01Recessed fluorescent luminaire without lens0.680.480.740.64
luminaire_heat_fractionsluminaire_02Recessed fluorescent luminaire with lens0.730.610.50.4
luminaire_heat_fractionsluminaire_03Downlight compact fluorescent luminaire10.950.240.12