Cooling Load Factors: cooking_gas_unhooded

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor_type: cooking_gas_unhooded3 rows
factor typeitem idapplianceenergy rate rated W (W)energy rate standby W (W)energy sourceheat gain sensible radiant W (W)hood typeradiation factor (dimensionless)usage factor (dimensionless)
cooking_gas_unhoodedgas_unhooded_001Broiler: underfired 900 mm10,8149,056Gas3,165Unhooded0.350.84
cooking_gas_unhoodedgas_unhooded_002Cheesemelter*3,6053,488Gas1,348Unhooded0.390.97
cooking_gas_unhoodedgas_unhooded_003Fryer, kettle29,014528Gas147Unhooded0.280.02