Cooling Load Factors: heat_gain_rad_conv

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor_type: heat_gain_rad_conv3 rows
factor typeitem idconvective fractionconvective fraction maxconvective fraction minheat gain typeradiative fractionradiative fraction max (dimensionless)radiative fraction min (dimensionless)
heat_gain_rad_convhg_010.400.4Occupants, typical office conditions0.600.6
heat_gain_rad_convhg_020.9 to 0.20.20.9Equipment0.1 to 0.80.80.1
heat_gain_rad_convhg_030.900.9Office, with fan0.100.1