ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor_type: cooking_electric_unhooded3 rows
factor typeitem idapplianceenergy rate cooking W (W)energy rate rated W (W)energy sourceheat gain latent W (W)heat gain sensible convective W (W)heat gain sensible radiant W (W)heat gain total W (W)hood typeradiation factor (dimensionless)usage factor (dimensionless)
cooking_electric_unhoodedelec_unhooded_001Cheesemelter2,7142,400Electric5991,0944432,136Unhooded0.161.13
cooking_electric_unhoodedelec_unhooded_002Egg cooker1,1912,380Electric630369651,065Unhooded0.050.5
cooking_electric_unhoodedelec_unhooded_003Fryer, countertop, open deep fryer3,8184,600Electric1,6294922022,323Unhooded0.050.83