Cooling Load Factors: warewashing

warewash 011 to warewash 020

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: warewashing8 rowsPage 2 of 3
factor typeitem idapplianceheat gain latent W (W)heat gain sensible convective W (W)heat gain sensible radiant W (W)heat gain total W (W)sub typesupply water flow rate Ls (L/s)usage factor (dimensionless)water temperature C (C)
warewashingwarewash 011Under-counter dishwasher1,3481,17202,520high temperature0.05182
warewashingwarewash 012Under-counter dishwasher3226450967high temperature with heat recovery0.04182
warewashingwarewash 013Upright door type1,02693801,964low temperature dump and fill0.06149
warewashingwarewash 014Upright door type3,8691,14305,012low temperature with tank0.04160
warewashingwarewash 015Upright door type6,2722,34508,616high temperature0.06182
warewashingwarewash 016Upright door type3,8101,40705,217high temperature with heat recovery0.06182
warewashingwarewash 0191120 mm Conveyor dishwasher17,3792,931020,310unvented0.11182
warewashingwarewash 0201680 mm Conveyor dishwasher13,1884,718017,907unvented0.11182