Cooling Load Factors: lighting power density

lpd 021 to lpd 030

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: lighting power density10 rowsPage 3 of 9
factor typeitem idlpd W per m2 (W/m2)space type
lighting power densitylpd 0217.3Patient room
lighting power densitylpd 0229.8Physical therapy room
lighting power densitylpd 0237.8Religious building
lighting power densitylpd 0244.5Health care facility
lighting power densitylpd 02513.5Recovery room
lighting power densitylpd 0263.5Sports arena
lighting power densitylpd 0276.3All other lounges/breakrooms
lighting power densitylpd 0282.5All other audience seating areas
lighting power densitylpd 02910.3Reading area
lighting power densitylpd 0306.5Banking Activity Area