Cooling Load Factors: lighting power density

lpd 011 to lpd 020

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: lighting power density10 rowsPage 2 of 9
factor typeitem idlpd W per m2 (W/m2)space type
lighting power densitylpd 0116.5Auditorium
lighting power densitylpd 0122.5Motion picture theater
lighting power densitylpd 0139.9Nursery
lighting power densitylpd 0142.5Gymnasium
lighting power densitylpd 01513.5Performing arts theater
lighting power densitylpd 01612.6Nurses' station
lighting power densitylpd 0179All other lobbies
lighting power densitylpd 01824.3Operating room
lighting power densitylpd 0197.2Penitentiary
lighting power densitylpd 0205.6Locker Room