Cooling Load Factors: lighting power density

lpd 031 to lpd 040

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: lighting power density10 rowsPage 4 of 9
factor typeitem idlpd W per m2 (W/m2)space type
lighting power densitylpd 0318Enclosed and ≤23.2 m²
lighting power densitylpd 03212.7Stacks
lighting power densitylpd 0337.1Enclosed and >23.2 m²
lighting power densitylpd 0346.6Open plan
lighting power densitylpd 0358.6Detailed manufacturing area
lighting power densitylpd 0361.6Parking Area, Interior
lighting power densitylpd 0378.2Equipment room
lighting power densitylpd 0387.6All other classrooms/lecture halls/
lighting power densitylpd 03917.9Pharmacy Area
lighting power densitylpd 04015.3Extra-high-bay area