Cooling Load Factors: below grade wall

wall d1p8 R0p88 to wall d2p4 R1p76

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: below grade wall10 rowsPage 3 of 4
factor typeitem iddepth below grade m (m)insulation levelu factor W per m2K (W/(m2·K))
below grade wallwall d1p8 R0p881.8R-0.880.505
below grade wallwall d1p8 R1p761.8R-1.760.343
below grade wallwall d1p8 R2p641.8R-2.640.262
below grade wallwall d1p8 Uninsulated1.8Uninsulated1.075
below grade wallwall d2p1 R0p882.1R-0.880.476
below grade wallwall d2p1 R1p762.1R-1.760.328
below grade wallwall d2p1 R2p642.1R-2.640.252
below grade wallwall d2p1 Uninsulated2.1Uninsulated0.98
below grade wallwall d2p4 R0p882.4R-0.880.45
below grade wallwall d2p4 R1p762.4R-1.760.315