Cooling Load Factors: below grade wall

wall d2p4 R2p64 to wall d2p4 Uninsulated

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: below grade wall2 rowsPage 4 of 4
factor typeitem iddepth below grade m (m)insulation levelu factor W per m2K (W/(m2·K))
below grade wallwall d2p4 R2p642.4R-2.640.244
below grade wallwall d2p4 Uninsulated2.4Uninsulated0.902