Cooling Load Factors: below grade wall

wall d0p9 R2p64 to wall d1p5 Uninsulated

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: below grade wall10 rowsPage 2 of 4
factor typeitem iddepth below grade m (m)insulation levelu factor W per m2K (W/(m2·K))
below grade wallwall d0p9 R2p640.9R-2.640.296
below grade wallwall d0p9 Uninsulated0.9Uninsulated1.571
below grade wallwall d1p2 R0p881.2R-0.880.579
below grade wallwall d1p2 R1p761.2R-1.760.379
below grade wallwall d1p2 R2p641.2R-2.640.283
below grade wallwall d1p2 Uninsulated1.2Uninsulated1.353
below grade wallwall d1p5 R0p881.5R-0.880.539
below grade wallwall d1p5 R1p761.5R-1.760.36
below grade wallwall d1p5 R2p641.5R-2.640.272
below grade wallwall d1p5 Uninsulated1.5Uninsulated1.195