Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Clearance Creepage: reinforced

reinf pd2 ovc3 600 to reinf pd3 ovc2 600

Minimum electrical clearance and creepage distances per IEC 60664-1:2020 (insulation coordination for low-voltage equipment up to 1000V AC / 1500V DC) and IPC-2221B (PCB conductor spacing). Indexed by insulation type (functional, basic, supplementary, reinforced, double, ipc_pcb), pollution degree (1–3), overvoltage category (I–IV), and working voltage (V). Clearance is shortest air-path distance; creepage is shortest surface-path distance. Critical for PCB layout, enclosure design, and product safety compliance (CE, UL, CSA).

Electrical Engineeringinsulation type: reinforced3 rowsPage 2 of 2
insulation typerecord idaltitude correction factorapplication noteclearance mm (mm)creepage mm (mm)material groupovervoltage categorypollution degreestandardworking voltage V (V)
reinforcedreinf pd2 ovc3 6001Reinforced insulation; PD2; OVC III; 600V; 5.5mm clearance5.56.4IIII2IEC60664-1600
reinforcedreinf pd3 ovc2 2501Reinforced insulation; PD3; OVC II; 250V; creepage more than doubled vs basic due to pollution26.4III3IEC60664-1250
reinforcedreinf pd3 ovc2 6001Reinforced insulation; PD3; OVC II; 600V; high creepage for industrial isolation412.5III3IEC60664-1600