E12-722 — Circuit Breaker
- Equipment Type
- Circuit Breaker
- Class Code
- E12-722
- Description
- Circuit breaker, vacuum, < 15
- Failure Rate per Year (failures/year)
- 0.039062
- Failures (count)
- 28
- Mdt Hours (h)
- 0.49
- Mtbf Hours (h)
- 224,259
- Mttm Hours (h)
- 0.35
- Mttr Hours (h)
- 9.39
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 716.8
Source: IEEE Std 3006.8-2018 Table 2