Explore the Engineering Database more efficiently by signing up for free. Sign up free
E12-311 — Circuit Breaker
- Equipment Type
- Circuit Breaker
- Class Code
- E12-311
- Description
- Circuit breaker, Fixed (molded
- Failure Rate per Year (failures/year)
- 0.000142
- Failures (count)
- 1
- Mdt Hours (h)
- 1
- Mtbf Hours (h)
- 61,560,528
- Mttr Hours (h)
- 1
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 7,027.5
Source: IEEE Std 3006.8-2018 Table 2