E12-711 — Circuit Breaker
- Equipment Type
- Circuit Breaker
- Class Code
- E12-711
- Description
- Circuit breaker, vacuum, < 15
- Failure Rate per Year (failures/year)
- 0.005832
- Failures (count)
- 3
- Mdt Hours (h)
- 0.06
- Mtbf Hours (h)
- 1,501,968
- Mttm Hours (h)
- 0.05
- Mttr Hours (h)
- 5.33
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 514.4
Source: IEEE Std 3006.8-2018 Table 2