Explore the Engineering Database more efficiently by signing up for free. Sign up free
E12-721 — Circuit Breaker
- Equipment Type
- Circuit Breaker
- Class Code
- E12-721
- Description
- Circuit breaker, vacuum, < 15
- Failure Rate per Year (failures/year)
- 0.044031
- Failures (count)
- 65
- Mdt Hours (h)
- 14.89
- Mtbf Hours (h)
- 198,950
- Mttm Hours (h)
- 2.6
- Mttr Hours (h)
- 11.58
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 1,476.2
Source: IEEE Std 3006.8-2018 Table 2