Equipment Failure Rates: Circuit_Breaker

Equipment failure rates, MTBF, MTTR, and downtime statistics for electrical and mechanical plant equipment. Primary data from the USACE PREP reliability database (IEEE Std 3006.8-2018 Table 2), covering ~280 equipment classes. Supplemental data from IEEE motor and transformer surveys.

Electrical Engineeringequipment_type: Circuit_Breaker3 rows
equipment typeclass codedescriptionfailure rate per year (failures/year)failures (count)mdt hours (h)mtbf hours (h)mttm hours (h)mttr hours (h)standardsurveyunit years (unit-years)
Circuit_BreakerE12-111Circuit breaker, air, 3-phase,0.0101289060.16864,88973.2711.65IEEE Std 3006.8-2018 Table 2USACE_PREP8,885.8
Circuit_BreakerE12-112Circuit breaker, air, 3-phase,0.0237083369,496IEEE Std 3006.8-2018 Table 2USACE_PREP126.5
Circuit_BreakerE12-211Circuit breaker, fixed (includes0.00011649.6475,706,5293.0923.25IEEE Std 3006.8-2018 Table 2USACE_PREP34,569.2

This is a sample. Search the full equipment failure rates dataset and 350+ more by creating a free account and accessing the database.