Explore the Engineering Database more efficiently by signing up for free. Sign up free
E12-211 — Circuit Breaker
- Equipment Type
- Circuit Breaker
- Class Code
- E12-211
- Description
- Circuit breaker, Fixed (includes
- Failure Rate per Year (failures/year)
- 0.000116
- Failures (count)
- 4
- Mdt Hours (h)
- 9.64
- Mtbf Hours (h)
- 75,706,529
- Mttm Hours (h)
- 3.09
- Mttr Hours (h)
- 23.25
- Standard
- IEEE Std 3006.8-2018 Table 2
- Survey
- Usace Prep
- Unit Years (unit-years)
- 34,569.2
Source: IEEE Std 3006.8-2018 Table 2