Cooling Load Factors: roof cts

number 31 to number 37

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: roof cts7 rowsPage 4 of 4
factor typeitem idassembly number (dimensionless)ctf h00 pctctf h01 pctctf h02 pctctf h03 pctctf h04 pctctf h05 pctctf h06 pctctf h07 pctctf h08 pctctf h09 pctctf h10 pctctf h11 pctctf h12 pctctf h13 pctctf h14 pctctf h15 pctctf h16 pctctf h17 pctctf h18 pctctf h19 pctctf h20 pctctf h21 pctctf h22 pctctf h23 pctdescriptiontotal R m2K per W ((m2·K)/W)u value W per m2K (W/(m2·K))
roof ctsnumber 31312.82.62.52.73.34.14.95.45.75.75.75.55.35.14.94.64.44.13.93.73.53.33.12.96.120.163
roof ctsnumber 323222.44.46.26.96.86.46.15.75.354.74.44.13.93.63.43.232.82.62.52.32.23.170.315
roof ctsnumber 33332.42.22.63.755.86.26.26.15.85.55.24.94.64.44.13.93.63.43.232.82.72.55.820.172
roof ctsnumber 34342.62.63.44.75.55.85.85.75.55.354.84.64.44.243.83.63.53.33.232.92.83.20.312
roof ctsnumber 35352.92.82.83.34.14.85.35.55.55.55.35.14.94.74.54.34.243.83.63.53.33.235.850.171
roof ctsnumber 36361.43.26.98.38.17.56.96.35.85.34.84.443.73.43.12.82.62.42.221.81.61.54.180.239
roof ctsnumber 37371.52.15.17.58.17.77.26.66.15.55.14.64.33.93.63.332.72.52.32.11.91.81.67.530.133