Cooling Load Factors: roof_cts

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor_type: roof_cts3 rows
factor typeitem idassembly number (dimensionless)ctf h00 pctctf h01 pctctf h02 pctctf h03 pctctf h04 pctctf h05 pctctf h06 pctctf h07 pctctf h08 pctctf h09 pctctf h10 pctctf h11 pctctf h12 pctctf h13 pctctf h14 pctctf h15 pctctf h16 pctctf h17 pctctf h18 pctctf h19 pctctf h20 pctctf h21 pctctf h22 pctctf h23 pctdescriptiontotal R m2K per W ((m2·K)/W)u value W per m2K (W/(m2·K))
roof_ctsnumber_01115.453.622.66.11.60.40.100000000000000000Metal Roof R-3.3 Batt Insulation Gyp. Board4.020.249
roof_ctsnumber_0224.239.135.914.24.61.40.40.10000000000000000Metal Roof R-6.7 Batt Insulation Gyp. Board7.370.136
roof_ctsnumber_03325.662.710.80.800000000000000000000Metal Roof R-3.3 Batt Insulation Suspended Acoustical Ceiling4.410.227