Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Cooling Load Factors: motor efficiency multi

kW1p5 poles8 enclosed to kW22p0 poles2 open

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: motor efficiency multi10 rowsPage 8 of 19
factor typeitem idfull load efficiency pct (%)motor kW (kW)motor typenum poles (dimensionless)
motor efficiency multikW1p5 poles8 enclosed841.5Enclosed8
motor efficiency multikW1p5 poles8 open86.51.5Open8
motor efficiency multikW224p0 poles2 enclosed95.8224Enclosed2
motor efficiency multikW224p0 poles2 open95.4224Open2
motor efficiency multikW224p0 poles4 enclosed96.2224Enclosed4
motor efficiency multikW224p0 poles4 open95.8224Open4
motor efficiency multikW224p0 poles6 enclosed95.8224Enclosed6
motor efficiency multikW224p0 poles6 open95.8224Open6
motor efficiency multikW22p0 poles2 enclosed91.722Enclosed2
motor efficiency multikW22p0 poles2 open91.722Open2

What else is in Engineering Database

Calculators that use this data

Related data