ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: motor efficiency multi10 rowsPage 7 of 19
factor typeitem idfull load efficiency pct (%)motor kW (kW)motor typenum poles (dimensionless)
motor efficiency multikW1p1 poles6 enclosed87.51.1Enclosed6
motor efficiency multikW1p1 poles6 open86.51.1Open6
motor efficiency multikW1p1 poles8 enclosed78.51.1Enclosed8
motor efficiency multikW1p1 poles8 open771.1Open8
motor efficiency multikW1p5 poles2 enclosed85.51.5Enclosed2
motor efficiency multikW1p5 poles2 open85.51.5Open2
motor efficiency multikW1p5 poles4 enclosed86.51.5Enclosed4
motor efficiency multikW1p5 poles4 open86.51.5Open4
motor efficiency multikW1p5 poles6 enclosed88.51.5Enclosed6
motor efficiency multikW1p5 poles6 open87.51.5Open6