Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Cooling Load Factors: cooking gas unhooded

gas unhooded 011 to gas unhooded 020

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: cooking gas unhooded10 rowsPage 2 of 3
factor typeitem idapplianceenergy rate rated W (W)energy rate standby W (W)energy sourceheat gain sensible radiant W (W)hood typeradiation factor (dimensionless)usage factor (dimensionless)
cooking gas unhoodedgas unhooded 011Induction wok*3,4880Gas0Unhooded00
cooking gas unhoodedgas unhooded 012Oven, combi: combi-mode*16,4111,612Gas234Unhooded0.150.1
cooking gas unhoodedgas unhooded 013Combi: convection mode16,4121,612Gas410Unhooded0.250.1
cooking gas unhoodedgas unhooded 014Oven, convection full-size12,1031,964Gas440Unhooded0.220.16
cooking gas unhoodedgas unhooded 015Convection half-size*5,5101,084Gas147Unhooded0.140.2
cooking gas unhoodedgas unhooded 016Pasta cooker*22,0102,491Gas0Unhooded00.11
cooking gas unhoodedgas unhooded 017Range top, top off/oven on*4,8651,172Gas293Unhooded0.250.24
cooking gas unhoodedgas unhooded 0183 elements on/oven off15,0054,513Gas1,846Unhooded0.410.3
cooking gas unhoodedgas unhooded 0196 elements on/oven off15,0059,730Gas4,074Unhooded0.420.65
cooking gas unhoodedgas unhooded 0206 elements on/oven on19,87010,668Gas4,250Unhooded0.40.54

What else is in Engineering Database