Cooling Load Factors: below grade floor

floor d1p8 w6 to floor d2p1 w9

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: below grade floor8 rowsPage 3 of 3
factor typeitem iddepth below grade m (m)floor width m (m)u factor W per m2K (W/(m2·K))
below grade floorfloor d1p8 w61.860.202
below grade floorfloor d1p8 w71.870.188
below grade floorfloor d1p8 w81.880.176
below grade floorfloor d1p8 w91.890.166
below grade floorfloor d2p1 w62.160.187
below grade floorfloor d2p1 w72.170.175
below grade floorfloor d2p1 w82.180.164
below grade floorfloor d2p1 w92.190.155