Cooling Load Factors: below grade floor

floor d0p9 w8 to floor d1p5 w9

ASHRAE cooling load calculation factors — people heat gain, lighting power density, luminaire heat fractions, motor efficiency, cooking/warewashing appliance heat gain, office/computer equipment heat gain, glazing optical properties, radiative/convective fractions, surface solar absorptance, wall and roof conduction time series (CTS), construction material layer properties, radiant time series (RTS), zone characteristics, and below-grade heat transfer coefficients. Source: ASHRAE Handbook Fundamentals 2021, Chapter 18.

Mechanical Engineeringfactor type: below grade floor10 rowsPage 2 of 3
factor typeitem iddepth below grade m (m)floor width m (m)u factor W per m2K (W/(m2·K))
below grade floorfloor d0p9 w80.980.23
below grade floorfloor d0p9 w90.990.215
below grade floorfloor d1p2 w61.260.242
below grade floorfloor d1p2 w71.270.224
below grade floorfloor d1p2 w81.280.208
below grade floorfloor d1p2 w91.290.195
below grade floorfloor d1p5 w61.560.22
below grade floorfloor d1p5 w71.570.204
below grade floorfloor d1p5 w81.580.19
below grade floorfloor d1p5 w91.590.179