Chiller Performance: chiller_scroll_air_cooled
Chiller and heat pump performance data — COP, EER, kW/ton at various capacities for air-cooled, water-cooled, centrifugal, screw, scroll, and heat pump equipment per AHRI 550/590 and ASHRAE 90.1
| equipment type | capacity tons | ashrae 901 min kw per ton fl (kW/ton) | ashrae 901 min kw per ton iplv (kW/ton) | compressor type | cop full load (dimensionless) | cop iplv (dimensionless) | eer full load (Btu/Wh) | eer iplv (Btu/Wh) | entering condenser temp F (F) | kw per ton full load (kW/ton) | kw per ton iplv (kW/ton) | leaving chilled water F (F) | notes | refrigerant |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| chiller_scroll_air_cooled | 5 | 1.168 | 0.862 | scroll | 2.93 | 3.87 | 10 | 13.21 | 95 | 1.2 | 0.907 | 44 | Multiple-scroll; small commercial; EER=10.0 at ARI conditions; air-cooled condensing | R-410A |
| chiller_scroll_air_cooled | 10 | 1.168 | 0.862 | scroll | 2.96 | 3.98 | 10.1 | 13.6 | 95 | 1.168 | 0.868 | 44 | Multiple-scroll; 10-ton air-cooled; standard code-minimum EER 10.1 | R-410A |
| chiller_scroll_air_cooled | 20 | 1.168 | 0.862 | scroll | 3.06 | 4.18 | 10.45 | 14.27 | 95 | 1.126 | 0.826 | 44 | Multiple-scroll; 20-ton class; good availability from all major OEMs | R-410A |