Home/Reference Data/Chiller Performance/chiller_scroll_air_cooled

Chiller Performance: chiller_scroll_air_cooled

Chiller and heat pump performance data — COP, EER, kW/ton at various capacities for air-cooled, water-cooled, centrifugal, screw, scroll, and heat pump equipment per AHRI 550/590 and ASHRAE 90.1

Mechanical Engineeringequipment_type: chiller_scroll_air_cooled3 rows
equipment typecapacity tonsashrae 901 min kw per ton fl (kW/ton)ashrae 901 min kw per ton iplv (kW/ton)compressor typecop full load (dimensionless)cop iplv (dimensionless)eer full load (Btu/Wh)eer iplv (Btu/Wh)entering condenser temp F (F)kw per ton full load (kW/ton)kw per ton iplv (kW/ton)leaving chilled water F (F)notesrefrigerant
chiller_scroll_air_cooled51.1680.862scroll2.933.871013.21951.20.90744Multiple-scroll; small commercial; EER=10.0 at ARI conditions; air-cooled condensingR-410A
chiller_scroll_air_cooled101.1680.862scroll2.963.9810.113.6951.1680.86844Multiple-scroll; 10-ton air-cooled; standard code-minimum EER 10.1R-410A
chiller_scroll_air_cooled201.1680.862scroll3.064.1810.4514.27951.1260.82644Multiple-scroll; 20-ton class; good availability from all major OEMsR-410A

This is a sample. Search the full chiller performance dataset and 300+ more by creating a free account and accessing the database.