Chiller Performance: ashrae_901_2022_min_air_cooled
Chiller and heat pump performance data — COP, EER, kW/ton at various capacities for air-cooled, water-cooled, centrifugal, screw, scroll, and heat pump equipment per AHRI 550/590 and ASHRAE 90.1
| equipment type | capacity tons | ashrae 901 min kw per ton fl (kW/ton) | ashrae 901 min kw per ton iplv (kW/ton) | compressor type | cop full load (dimensionless) | cop iplv (dimensionless) | eer full load (Btu/Wh) | eer iplv (Btu/Wh) | entering condenser temp F (F) | kw per ton full load (kW/ton) | kw per ton iplv (kW/ton) | leaving chilled water F (F) | notes | refrigerant |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ashrae_901_2022_min_air_cooled | 10 | 1.168 | 0.862 | air_cooled | 2.96 | 4.02 | 10.1 | 13.72 | 95 | 1.168 | 0.862 | 44 | ASHRAE 90.1-2022 Table 6.8.1-3 minimum: air-cooled chiller <150 tons; min EER 10.1 FL; min IPLV 13.7 EER | any |
| ashrae_901_2022_min_air_cooled | 200 | 1.168 | 0.843 | air_cooled | 2.96 | 4.1 | 10.1 | 14 | 95 | 1.168 | 0.843 | 44 | ASHRAE 90.1-2022 Table 6.8.1-3 minimum: air-cooled chiller >=150 tons; min EER 10.1 FL; min IPLV 14.0 EER | any |