Home/Reference Data/Chiller Performance/ashrae_901_2022_min_air_cooled

Chiller Performance: ashrae_901_2022_min_air_cooled

Chiller and heat pump performance data — COP, EER, kW/ton at various capacities for air-cooled, water-cooled, centrifugal, screw, scroll, and heat pump equipment per AHRI 550/590 and ASHRAE 90.1

Mechanical Engineeringequipment_type: ashrae_901_2022_min_air_cooled2 rows
equipment typecapacity tonsashrae 901 min kw per ton fl (kW/ton)ashrae 901 min kw per ton iplv (kW/ton)compressor typecop full load (dimensionless)cop iplv (dimensionless)eer full load (Btu/Wh)eer iplv (Btu/Wh)entering condenser temp F (F)kw per ton full load (kW/ton)kw per ton iplv (kW/ton)leaving chilled water F (F)notesrefrigerant
ashrae_901_2022_min_air_cooled101.1680.862air_cooled2.964.0210.113.72951.1680.86244ASHRAE 90.1-2022 Table 6.8.1-3 minimum: air-cooled chiller <150 tons; min EER 10.1 FL; min IPLV 13.7 EERany
ashrae_901_2022_min_air_cooled2001.1680.843air_cooled2.964.110.114951.1680.84344ASHRAE 90.1-2022 Table 6.8.1-3 minimum: air-cooled chiller >=150 tons; min EER 10.1 FL; min IPLV 14.0 EERany

This is a sample. Search the full chiller performance dataset and 300+ more by creating a free account and accessing the database.

Get started for FREE

Related data